Index      Products     Technical details



 Technical details
 
Basic electrical heaters



  Models

  S 2   S 3   S 6   S 10   S 17
.
  power  kW   2 / 1      3,5 / 1,75   6,3   10   16,4 / 10
  voltage  V   230   230   400   3 phase   400  3 phase   400  3 phase
  front fuse  A   10   16   10   16   25
  connecting plug   230 V 16 A   230 V 16 A   400 V 16 A   400 V 16 A   400 V 32 A
  air flow  m3 / h   150   570   560   930   1140
  temp. rise  C   38   17   31   30   40
.
  thermostat controlled
  cool down   no   no   yes   yes   yes
  fan bearing   slide   slide   slide   ball   ball
.
  measurements:
    length mm   250   350   440   500   667
    width mm   180   270   270   320   320
    height mm   300   400   400   530   530
    weight kg   5,5   10   13   19   25
.
  heated 
  space m3  (average)   80   140   260   400   680
.
.
   models   S 2  -  S 17  also include:
   
  cool air flow   continuous air flow with no heat on
  continuous air flow   continuous air flow,  thermostat controls the temperature
  air flow when heating   thermostat controls fan and heating elements both  (including cooldown operation)
  thermostat   Celsius scale controlled thermostat 0 - 40 degrees centigrade
-
  qualified for   dry and humid surroundings
  protection degree   IP 54,  dust- and splash protected
  qualifications   FI,  EMC,  CE
.
  cover material   powder painted steel casing
  heating elements   stainless steel covered coils   ( coils covered by lamelled metal tubes in model S 2  )










 Technical details
  heaters for combustible conditions



  Models

  S 3 PVT   S 5 PVT   S 8 PVT
.
  power  kW   3,5 / 1,75   5,5   8 / 4
  voltage  V   230   400   3 phase   400  3 phase
  front fuse  A   16   10   16
  connecting plug   230 V 16 A   400 V 16 A   400 V 16 A
  air flow  m3 / h   810   900   820
  temp. rise  C   12   17   27
.
  thermostat controlled
  cool down   no   yes   yes
  fan bearing   slide   ball   ball
.
  measurements:
    length mm   410   500   667
    width mm   270   320   320
    height mm   380   530   530
    weight kg   9   19   25
.
  heated
  space m3  (average)   140   220   320
.

 

  All PVT-models also include:
 
  cool air flow   continuous air flow with no heat on
  continuous air flow   continuous air flow,  thermostat controls the temperature
  air flow when heating   thermostat controls fan and heating elements both  (including cooldown operation)
  thermostat   Celsius scale controlled thermostat 0 - 40 degrees centigrade
-
  qualified for   dry and humid surroundings and combustible conditions
  protection degree   IP 54,  dust- and splash protected
  qualifications   FI,  EMC,  CE
.
  cover material   stainless steel 
  heating elements   stainless steel covered coils 


  
.
.

  Wall racks   ST 10   ST 20
  for models   S 3,   S 6,   S 10  , S 3 PVT   and   S 5 PVT   S 17   and   S 8 PVT


  
  

  SIURA OY
 
  
 


Index      Products     Technical details